Archive 2016 NA CATALOG
EPIC ® Pin & Sleeve Connectors Test Data & Cable Outer Diameter Accommodation
Technical Data
Table 2: Endurance Test
Table 1: Ground Path Current Test
A test current that far exceeds the device rating is passed through the mating device and grounding wires.
The test sequence is conducted using a no-load, followed by a loading sequence. The power factor of the load is 0.75 - 0.80.
Grounding Conductor Min. Size
Time (sec)
Test Current
Device Rating
Cycles with Load @ Rated Current & Voltage
Device Rating
No-Load Cycles
Sequence
(mm ² )
(A)
(AWG)
20/16A 30/32A 60/63A
5000 1000 1000
0
—
20/16A 30/32A 60/63A
12 10 10
3.3 5.3 5.3 8.4
4 4 4 4
470 750 750
1000 1000
Alternating Alternating Alternating
100/125A
250
250
100/125A
8
1180
Table 4: Withdrawal Force Test
Table 3: Cable Security Test
The flexible cord or cable is simultaneously twisted and pulled. Values for the applied twisting torque and force of pull are shown. In all cases, the cord displacement is less than 3 ⁄ 32 ”
The pressure exerted by mating contacts of a plug and a connector must be sufficient to prevent unintentional withdrawal during normal use. During the test any locked rings or retaining means are not engaged.
Force
Torque
Max. Displacement
Device Rating
(lb)
(N)
(ft/lb)
(N/m)
(in)
(mm)
Min. Withdrawal Force (lb) (N)
Device Rating
20/16A 30/32A 60/63A
30 75
133 333
0.4 0.54 3/32 2.38 0.5 0.68 3/32 2.38
20/16A 30/32A 60/63A
5 6
22 27 67 89
150 667
1.0 2.0
1.4 3/32 2.38 2.7 3/32 2.38
100/125A 150 667
15 20
100/125A
Table 5: Cable Outer Diameter Accommodation
Cable Diameter Range: 2+PE
Cable Diameter Range: 3+PE
Cable Diameter Range: 3+N+PE
Sleeve/ Cable Gland
Device Rating & Configuration
(in)
(mm)
(in)
(mm)
(in)
(mm)
EPIC ® MULTIMAX Series 20/16A
— — —
0.32 - 0.55 0.45 - 0.68 0.67 - 1.02
8.1 - 14.0 11.5 - 17.3 17.0 - 26.0
0.33 - 0.55 0.49 - 0.76 0.75 - 1.13
8.5 - 14.0 12.5 - 19.3 19.0 - 28.6
0.39 - 0.60 0.55 - 0.84 0.83 - 1.24
10.0 - 15.3 14.0 - 21.3 21.0 - 31.5
30/32A
63A
EPIC ® CEE Series 20/16A: 2P+PE 20/16A: 3P+PE 20/16A: 3P+N+PE
PG 13 PG 16 PG 16 PG 21 PG 29 NPT 2” PG 29* PG 29*
0.32 - 0.53
8.1 - 13.5
—
—
— —
— —
— —
— —
0.35 - 0.60
8.8 - 15.3
—
—
0.35 - 0.60 0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98 0.47 - 0.63 0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02 —
8.8 - 15.3 11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0 12.0 - 16.0 9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0 —
30/32A 60/63A
0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98
11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0
0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98
11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0
100/125A
EPIC ® ULYSSE Series 20/16A
30/32A 60/63A
2x PG 29*
EPIC ® ALUPRES Series 20/16A: 2+PE, 3+PE
FO-NPT ½” FO-NPT ¾” F1-NPT ½” F1-NPT ¾” F1-NPT 1” F1-NPT 1¼”
0.35 - 0.47
9.0 - 12.0
0.35 - 0.47
9.0 - 12.0
20/16A: 3+N+PE
—
—
—
—
0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02
9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0
0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02
9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0
30/32A & 60/63A (order flanges separately)
* Unthreaded entry hole. Cable ODs are based on switched-socket accessory strain relief (ordered separately). See page 475 for required strain relief and locknut.
Table 6: Wire Size Accommodation
Recommended Torque for CEE Contact Set Screws
Recommended Torque for MULTIMAX Contact Set Screws
Max. Wire Size*
Device Rating
(mm 2 )
(ft/lb)
(N/m)
(ft/lb)
(N/m)
(AWG)
20/16A 30/32A 60/63A
12
4
0.60
0.8
0.60 1.48
0.8 2.0
8 6 1
10 16 50
2x 0.60 2x 1.48 2x 2.95
2x 0.8 2x 2.0 2x 4.0
— —
— —
100/125A
* subject to stranding configuration.
800-774-3539 • www.lappusa.com • www.lappcanada.com • www.lappmexico.com
480
Made with FlippingBook - Online Brochure Maker