Archived 2016 Lapp Group International Catalog
T12 Technical Tables Current ratings – reduction tables
1132 ÖLFLEX ® ACCESSORIES FLEXIMARK ® SILVYN ® SKINTOP ® EPIC ® HITRONIC ® ETHERLINE ® UNITRONIC ® APPENDIX
H01N2-D and H01N2-E The values given in the table below are reference values and in a simplified form took out of the DIN VDE 0298 part 4, 2013-06, table 16. For copyright reasons, only excerpts from DIN VDE 0298 part 4 can be mapped at this point. Table 12-10: operating conditions and ratings for welding cables
Permissible operating temperature at the conductor 85°C
Ambient temperature: 30°C
Installation type: in the open air
Number of cores under load
1
Continuous operation
Mode of operation
Intermittent operation
Run time
-
5 minutes
Switch-on duration (ED)
100%
85%
80%
60%
35%
20%
8%
Rating A
Nominal cross-section of copper cond. in mm 2
10 16 25 35 50
96
97
98
102 142 196 250 323
114 166 234 304 398
137 204 293 384 508
198 301 442 584 779
130 173 216 274
132 179 226 287
134 181 229 293
Continuous operation
Mode of operation
Intermittent operation
Run time
-
10 minutes
Switch-on duration (ED)
100%
85%
80%
60%
35%
20%
8%
Rating A
Nominal cross-section of copper cond. in mm 2
10 16 25 35 50
96
96
96
97
102 144 204 268 356
113 167 244 324 439
152 233 351 477 654
130 173 216 274
131 175 220 281
131 176 222 284
133 182 233 303
Conversion factors for differing ambient temperature
Table T 12-2
For current information see: www.lappgroup.com