Connectivity Guide
VFD cable selection guide AWG size selection per NEC
Wire size is suggested based on horse power (HP) and the full load current (FLC) × 125% per NEC Art. 430-122 (A). FLC is determined from NEC Art. 430- 250.
Suggested AWG
Drive HP
230V 3Ø
460V 3Ø
575V 3Ø
½–2
16*, 14
16*, 14 16*, 14
16*, 14 16*, 14
3–5
14 10
7½–10
14 10 10
14 12 10 10
15
6 4 4 3 1
20 25 30 40 50 60 75
8 8 6 4 3 1
8 6 6 4 3 1
2/0 3/0
250 KCMIL 350 KCMIL
100 125 150 200 250 300
2/0 3/0 4/0
— — — — — —
2/0 3/0
350 KCMIL 500 KCMIL
250 KCMIL 350 KCMIL 500 KCMIL
— —
350–500
—
* 16 AWG may be used depending on compliance with the applicable sections of NEC. Final determination can only be provided by the local AHJ.