LAPP North America's current product catalog

EPIC ® Pin & sleeve connectors Test data & cable outer diameter accommodation

Technical data

Table 1: ground path current test

Table 2: endurance test

A test current that far exceeds the device rating is passed through the mating device and grounding wires.

The test sequence is conducted using a no-load, followed by a loading sequence. The power factor of the load is 0.75 - 0.80.

Device rating

Cycles with load @ rated current & voltage

No-load cycles

Grounding conductor min. size

Time

Test current

Device rating

Sequence

AWG

mm²

sec

A

20/16A 30/32A 60/63A

5000 1000 1000

0

20/16A 30/32A 60/63A

12 10 10

3.3 5.3 5.3 8.4

4 4 4 4

470 750 750

1000 1000

alternating alternating alternating

100/125A

250

250

100/125A

8

1180

Table 3: cable security test

Table 4: withdrawal force test

The flexible cord or cable is simultaneously twisted and pulled. Values for the applied twisting torque and force of pull are shown. In all cases, the cord displacement is less than 3 ⁄ 32 "

The pressure exerted by mating contacts of a plug and a connector must be sufficient to prevent unintentional withdrawal during normal use. During the test any locked rings or retaining means are not engaged.

Force

Torque

Max. displacement

Device rating

lb

N

ft/lb

N/m 0.54 0.68

in

mm

Min. withdrawal force lb N

Device rating

20/16A 30/32A 60/63A

30 75

133 333 667 667

0.4 0.5 1.0 2.0

3/32 3/32 3/32 3/32

2.38 2.38 2.38 2.38

20/16A 30/32A 60/63A

5 6

22 27 67 89

150 150

1.4 2.7

100/125A

15 20

100/125A

Table 5: cable outer diameter accommodation

Cable diameter range: 2+PE

Cable diameter range: 3+PE

Cable diameter range: 3+N+PE

Sleeve/ cable gland

Device rating & configuration

in

mm

in

mm

in

mm

EPIC ® MULTIMAX 20/16A

— — —

0.32 - 0.55 0.45 - 0.68 0.67 - 1.02

8.1 - 14.0 11.5 - 17.3 17.0 - 26.0

0.33 - 0.55 0.49 - 0.76 0.75 - 1.13

8.5 - 14.0 12.5 - 19.3 19.0 - 28.6

0.39 - 0.60 0.55 - 0.84 0.83 - 1.24

10.0 - 15.3 14.0 - 21.3 21.0 - 31.5

30/32A

63A

EPIC ® CEE

20/16A: 2P+PE 20/16A: 3P+PE 20/16A: 3P+N+PE

PG 13 PG 16 PG 16 PG 21 PG 29 NPT 2”

0.32 - 0.53

8.1 - 13.5

— —

— —

— —

— —

0.35 - 0.60

8.8 - 15.3

0.35 - 0.60 0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98 0.47 - 0.63 0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02 —

8.8 - 15.3 11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0 12.0 - 16.0 9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0 —

30/32A 60/63A

0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98

11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0

0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98

11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0

100/125A

EPIC ® ULYSSE 20/16A

PG 29* PG 29*

30/32A 60/63A

2x PG 29*

EPIC ® ALUPRES

20/16A: 2+PE, 3+PE 20/16A: 3+N+PE

FO-NPT ½” FO-NPT ¾” F1-NPT ½” F1-NPT ¾” F1-NPT 1” F1-NPT 1¼”

0.35 - 0.47

9.0 - 12.0

0.35 - 0.47

9.0 - 12.0

0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02

9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0

0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02

9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0

30/32A & 60/63A (order flanges separately)

* unthreaded entry hole. Cable ODs are based on switched-socket accessory strain relief (ordered separately). See page 479 for required strain relief and locknut.

Table 6: wire size accommodation

Recommended torque for CEE contact set screws

Recommended torque for MULTIMAX contact set screws

Max. wire size*

Device rating

AWG

mm²

ft/lb 0.60

N/m

ft/lb

N/m

20/16A 30/32A 60/63A

12

4

0.8

0.60 1.48

0.8 2.0

8 6 1

10 16 50

2x 0.60 2x 1.48 2x 2.95

2x 0.8 2x 2.0 2x 4.0

— —

— —

100/125A

* subject to stranding configuration.

for current information see: www.lappusa.com • www.lappcanada.com

484