LAPP North America's current product catalog
EPIC ® Pin & sleeve connectors Test data & cable outer diameter accommodation
Technical data
Table 1: ground path current test
Table 2: endurance test
A test current that far exceeds the device rating is passed through the mating device and grounding wires.
The test sequence is conducted using a no-load, followed by a loading sequence. The power factor of the load is 0.75 - 0.80.
Device rating
Cycles with load @ rated current & voltage
No-load cycles
Grounding conductor min. size
Time
Test current
Device rating
Sequence
AWG
mm²
sec
A
20/16A 30/32A 60/63A
5000 1000 1000
0
—
20/16A 30/32A 60/63A
12 10 10
3.3 5.3 5.3 8.4
4 4 4 4
470 750 750
1000 1000
alternating alternating alternating
100/125A
250
250
100/125A
8
1180
Table 3: cable security test
Table 4: withdrawal force test
The flexible cord or cable is simultaneously twisted and pulled. Values for the applied twisting torque and force of pull are shown. In all cases, the cord displacement is less than 3 ⁄ 32 "
The pressure exerted by mating contacts of a plug and a connector must be sufficient to prevent unintentional withdrawal during normal use. During the test any locked rings or retaining means are not engaged.
Force
Torque
Max. displacement
Device rating
lb
N
ft/lb
N/m 0.54 0.68
in
mm
Min. withdrawal force lb N
Device rating
20/16A 30/32A 60/63A
30 75
133 333 667 667
0.4 0.5 1.0 2.0
3/32 3/32 3/32 3/32
2.38 2.38 2.38 2.38
20/16A 30/32A 60/63A
5 6
22 27 67 89
150 150
1.4 2.7
100/125A
15 20
100/125A
Table 5: cable outer diameter accommodation
Cable diameter range: 2+PE
Cable diameter range: 3+PE
Cable diameter range: 3+N+PE
Sleeve/ cable gland
Device rating & configuration
in
mm
in
mm
in
mm
EPIC ® MULTIMAX 20/16A
— — —
0.32 - 0.55 0.45 - 0.68 0.67 - 1.02
8.1 - 14.0 11.5 - 17.3 17.0 - 26.0
0.33 - 0.55 0.49 - 0.76 0.75 - 1.13
8.5 - 14.0 12.5 - 19.3 19.0 - 28.6
0.39 - 0.60 0.55 - 0.84 0.83 - 1.24
10.0 - 15.3 14.0 - 21.3 21.0 - 31.5
30/32A
63A
EPIC ® CEE
20/16A: 2P+PE 20/16A: 3P+PE 20/16A: 3P+N+PE
PG 13 PG 16 PG 16 PG 21 PG 29 NPT 2”
0.32 - 0.53
8.1 - 13.5
—
—
— —
— —
— —
— —
0.35 - 0.60
8.8 - 15.3
—
—
0.35 - 0.60 0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98 0.47 - 0.63 0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02 —
8.8 - 15.3 11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0 12.0 - 16.0 9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0 —
30/32A 60/63A
0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98
11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0
0.45 - 0.84 0.63 - 1.12 1.02 - 1.93 0.71 - 0.98 0.71 - 0.98 0.71 - 0.98
11.5 - 21.3 16.0 - 28.5 26.0 - 49.0 18.0 - 25.0 18.0 - 25.0 18.0 - 25.0
100/125A
EPIC ® ULYSSE 20/16A
PG 29* PG 29*
30/32A 60/63A
2x PG 29*
EPIC ® ALUPRES
20/16A: 2+PE, 3+PE 20/16A: 3+N+PE
FO-NPT ½” FO-NPT ¾” F1-NPT ½” F1-NPT ¾” F1-NPT 1” F1-NPT 1¼”
0.35 - 0.47
9.0 - 12.0
0.35 - 0.47
9.0 - 12.0
—
—
—
—
0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02
9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0
0.35 - 0.47 0.55 - 0.63 0.63 - 0.87 0.98 - 1.02
9.0 - 12.0 14.0 - 160 16.0 - 22.0 25.0 - 26.0
30/32A & 60/63A (order flanges separately)
* unthreaded entry hole. Cable ODs are based on switched-socket accessory strain relief (ordered separately). See page 479 for required strain relief and locknut.
Table 6: wire size accommodation
Recommended torque for CEE contact set screws
Recommended torque for MULTIMAX contact set screws
Max. wire size*
Device rating
AWG
mm²
ft/lb 0.60
N/m
ft/lb
N/m
20/16A 30/32A 60/63A
12
4
0.8
0.60 1.48
0.8 2.0
8 6 1
10 16 50
2x 0.60 2x 1.48 2x 2.95
2x 0.8 2x 2.0 2x 4.0
— —
— —
100/125A
* subject to stranding configuration.
for current information see: www.lappusa.com • www.lappcanada.com
484
Made with FlippingBook flipbook maker