LAPP North America's current product catalog
Flexible cable for drives, motors & assemblies
VFD cable
VFD TGK SYMMETRICAL is a flexible VFD cable that ensures ease of routing in the industrial platform. Superior shielding minimizes EMI to surrounding system. The insulated ground conductors are symmetrically positioned to reduce the effects of common mode current on motor and drive. Symmetrical GND motor supply cable for VFD drives VFD TGK FLX SYMMETRICAL
Construction
Recommended applications
VFD drive & motor connections for large HP applications; pumps; compressors; conveyors; elevators; extruders; HVAC; large presses; on/off, slow down/speed up applications.
Conductors: bare copper Insulation: XLPE insulation + 3 insulated symetrical grounds Shielding: foil and tinned copper braid Jacket: TPE black
Approvals
Application advantage
• 85% foil and braid coverage for EMI & RFI protection • Low capacitance design • UL TC-ER approved with XHHW-2 insulated conductors • 3 SYM ground design for optimal electrical performance
Cable attributes
page 648
FR-03
OR-03
OIL
FLAME
MOTION FL-01
MP-03
MECH.
Technical data Minimum bend radius: Temperature range: - UL TC: - for stationary use:
Color code:
7.5 x OD
Black conductors with white numbers, plus 3 green/yellow symmetrical grounds.
-25°C to +90°C -40°C to +90°C
Approvals:
UL: TC-ER per UL 1277
Flexible motor supply cable per UL 2277 (12 AWG to 4/0)
Nominal voltage: - UL TC-ER:
600/1000V
Attributes: Oil Res I/II
- UL Flexible Motor Supply:
1000V
90°C wet or dry XHHW-2 per UL 44
Test voltage: 12 - 10 AWG
-40°C cold bend sunlight resistant direct burial NFPA 79 NEC: Class 1 Division 2 per NEC Article 501 Canada: c(UL) RW90/TC FT4 cRU AWM I/II A/B 90C FT4 Additional: RoHS II
6,000V 7,500V 9,000V 10,000V
8 - 2 AWG
1 AWG - 4/0
250 - 500 MCM
Conductor stranding: - Circuit
12 AWG to 500 KCMIL: Class K 16 AWG to 6 KCMIL: Class K
- Ground
3 symmetrical
Nominal outer diameter
3 symmetrical
Nominal outer diameter
Copper weight
Approx. weight lbs/mft
Copper weight
Approx. weight lbs/mft
SKINTOP ® MS-M BRUSH metric thread
SKINTOP ® MS-M BRUSH metric thread
Part number
Part number
grounds
in
mm lbs/mft
grounds
in
mm lbs/mft
1/0 AWG (53.7 mm²) 813437 10 AWG 1.326 33.7 1251 1678 53112679 2/0 AWG (67.7 mm²) 813438 10 AWG 1.456 37.0 1523 2003 53112680 3/0 AWG (70 mm²) 813439 8 AWG 1.616 41.0 1925 2474 53112680 4/0 AWG (95 mm²) 813440 8 AWG 1.700 43.18 2325 2959 53112680 250 KCMIL (177.9 mm²) 813441 8 AWG 1.890 48.0 2719 3588 53112681 350 KCMIL (185 mm²) 813442 6 AWG 2.182 55.4 3748 4762 53112501 500 KCMIL (254.1 mm²) 813443 6 AWG 2.490 63.2 5211 6412 53112500
12 AWG (3.30 mm²) 813430 16 AWG 0.461 11.71 152 10 AWG (5.32 mm²) 813431 14 AWG 0.522 13.3 213 8 AWG (8.52 mm²) 813432 14 AWG 0.706 17.9 286 6 AWG (13.5 mm²) 813433 12 AWG 0.802 20.4 415 4 AWG (21.0 mm²) 813434 12 AWG 0.899 22.8 574 2 AWG (33.7 mm²) 813435 10 AWG 1.117 28.4 873 1 AWG (35.0 mm²) 813436 10 AWG 1.203 30.6 1051
260
53112676
340
53112676
451
53112677
646
53112678
836
53112678
1189
53112679
1438
53112679
If not otherwise specified, all values relating to the product are nominal values. Photographs are not to scale and are not true representations of the products in question.
for current information see: www.lappusa.com • www.lappcanada.com
745